Liquiphant FTL64 HART Operation
Endress+Hauser 37
Parameter configuration (Operator user role):
Parameter configuration of the device is locked in the Operator user role.
Unlocking access:
Access to parameter configuration can be unlocked by entering the password. The user
role changes back to Maintenance.
Navigation for assigning the password and changing the user role: System → User
management
Delete password:
If necessary, the password can be deleted in the User management.
Navigation: System → User management → Delete password → Start
10 Operation
10.1 Reading off the device locking status
Displaying active write protection in the Locking status parameter
Local display  :
The symbol appears on the main page
Operating tool (FieldCare/DeviceCare)  :
Navigation: System → Device management → Locking status
10.2 Reading off measured values
All the measured values can be read off using the Measured values submenu.
Navigation: Application menu → Measured values submenu
10.3 Adapting the device to process conditions
The following menus are available for this purpose:
Basic settings in the Guidance menu
Advanced settings in:
Diagnostics menu
Application menu
System menu
10.3.1 Level limit detection
Operating as a point level switch in the 8/16 mA mode.
Output of point level:
8 mA (demand mode: MIN uncovered or MAX covered)
16 mA (OK status: MIN covered or MAX uncovered)
1. Navigation: Application → Sensor → Sensor configuration
2. Set the Mode of operation to Level limit detection.
3. Set the Safety function to MIN (dry-running prevention) or MAX (overfill protection),
according to the application.
4. Set the Density setting parameter according to the application (> 0.4 g/cm³, > 0.5 g/
cm³, > 0.7 g/cm³ ).
5. Optionally: Set the Switching delay uncovered to covered parameter and the
Switching delay covered to uncovered parameter.