Mounting Liquiphant FTL64 HART
14 Endress+Hauser
> 25 (0.98)
> 50 (1.97)!
A0042333
 6 Installation example for low-viscosity liquids. Unit of measurement mm (in)
High viscosity
NOTICE
Highly viscous liquids may cause switching delays.
Make sure that the liquid can run off the tuning fork easily.
Deburr the socket surface.
High viscosity, e.g. viscous oils: ≤ 10 000 mPa⋅s
The tuning fork must be located outside the installation socket!
> 40 (1.57)
A0042335
 7 Installation example for a highly viscous liquid. Unit of measurement mm (in)
5.1.4 Avoid buildup
Use short installation sockets to ensure that the tuning fork projects freely into the
vessel
Leave sufficient distance between the buildup expected on the tank wall and the tuning
fork