Commissioning Liquiphant FTL64 HART
34 Endress+Hauser
A0046404
Click "Settings" and select the desired language:
A0046406
Setting the language for the local display via DeviceCare
Navigation: System → Display → Language
Set the desired language in the Language parameter.
9.7 Device configuration
9.7.1 Commissioning with DIP switch and operating keys on the
electronic insert
Display
onoff
1
2
onoff
3
4
A0046573
 24 Operating keys and DIP switches on the 4 to 20 mA HART electronic insert
1 Operating key for reset password (for Bluetooth login and Maintenance user role)
1+2 Operating keys for device reset (as-delivered state)
2 Operating key for Proof test (> 3 s)
3 DIP switch for safety function, software-defined (SW, default=MAX) or set permanently to MIN
4 DIP switch for locking and unlocking the device
Setting the MIN or MAX safety mode via the DIP switch
When the switch is set to "SW", the MIN or MAX setting is defined by the software, with
MAX being the default value.
In the "MIN" switch position, the setting is permanently MIN irrespective of the software.