Liquistation CSF34 Operation
Endress+Hauser 111
Menu/Setup/Sampling programs
Function Options Info
Bottle synchronization Selection
• None
• 1. bottle change time
• 1. Time of change + bottle
number
• External BC sync input
Factory setting
None
Specific bottles can be assigned specific
filling times with the bottle synchronization
function. For example, bottle 1 is to be filled
from midnight to 2 a.m., bottle 2 from 2 a.m.
to 4 a.m. etc..
None
The sampling and bottle change times are
not synchronized.
1. bottle change time
Sampling starts with the first bottle. The
change to the next bottle is synchronized.
1. Time of change + bottle number
Each bottle is allocated a specific filling time.
External BC sync input
The system changes to the next bottle when
an external signal is received. The external
signal first has to be configured via the
binary input. The binary input can then be
selected as the source.
Assignment bin. output Selection
• No binary output
configured
• Binary output S:x
Factory setting
No binary output configured
Assignment of the binary output to the
program cycle.
Use "SAVE" to save the subprogram setup. Then press "ESC" to return to the main program.
Inputs Settings for the inputs can be made as
described in the "Inputs" section.
Bottle assignment
(only possible with
multiple bottles)
This menu item appears
when more than one
bottle is available,
regardless of the number
of subprograms.
Selection
• No bottle assignment
• Dynamic bottle assignment
• Statical bottle assignment
• Statical bottle assignment
Factory setting
Dynamic bottle assignment
No bottle assignment:
Each subprogram fills the same bottle until
the bottle is full. All the subprograms then
change to the next bottle. Only visible if
there is more than one subprogram.
Dynamic bottle assignment:
When the subprogram changes, the system
switches to the next empty bottle
Statical bottle assignment:
A table can be used to assign a subprogram
to each bottle
Via the "Bottle change" menu item, the bottle change can be configured after a certain time or number of
samples if bottle distribution with more than one bottle has been selected and either dynamic or static bottle
assignment has been selected.
Having selected Bottle assignmentStatical bottle assignment:
Bottle assignment table
Select a bottle and assign it a subprogram.
10.3.4 Selecting and executing the program
In the overview, under Select sampling program you can see all the programs created.
Here you can also use New to create a new program.
Using the navigator, you can select the program you want to execute here and then choose
from the following menu items:
• Edit
• Start
• Duplicate
• Cancel