Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 149
The parameters
Assign diagnostic signal 1/2 (11179)
Navigation Expert → Diagnostics → Advanced diagnostics → Assign diagnostic signal 1/2
Write access Maintenance
Descriptions Assigns a measuring variable, which is needed for diagnostic purposes, to the Advanced
Diagnostics Block.
Options • None
• Level linearized
• Unfiltered distance
• Relative echo amplitude
• Electronic temperature
• Measured current
• Terminal voltage
• Area of incoupling
Factory setting None
Link AD 1/2 to (11180)
Navigation Expert → Diagnostics → Advanced diagnostics → Link AD 1/2 to
Write access Maintenance
Descriptions Links the Advanced Diagnostics Block 1 or 2 to the other Advanced Diagnostics Block in
order to include the linking logic into the configuration (→ 144).
Options • None
• Digital output AD 1
• Digital output AD 2
Factory setting None
Linking logic AD 1/2 (11181)
Navigation Expert → Diagnostics → Advanced diagnostics → Linking logic AD 1/2
Write access Maintenance
Prerequisite Only visible if the Advanced Diagnostics Block has been linked to the digital oputput of the
other Advanced Diagnostics Block via the Link AD 1/2 to parameter.
Descriptions Defines the linking logic between the two Advanced Diagnostics Blocks AD1 and AD2.