EasyManua.ls Logo

Endress+Hauser Micropilot FMR56 - Page 149

Endress+Hauser Micropilot FMR56
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 149
The parameters
Assign diagnostic signal 1/2 (11179)
Navigation Expert → Diagnostics → Advanced diagnostics → Assign diagnostic signal 1/2
Write access Maintenance
Descriptions Assigns a measuring variable, which is needed for diagnostic purposes, to the Advanced
Diagnostics Block.
Options None
Level linearized
Unfiltered distance
Relative echo amplitude
Electronic temperature
Measured current
Terminal voltage
Area of incoupling
Factory setting None
Link AD 1/2 to (11180)
Navigation Expert → Diagnostics → Advanced diagnostics → Link AD 1/2 to
Write access Maintenance
Descriptions Links the Advanced Diagnostics Block 1 or 2 to the other Advanced Diagnostics Block in
order to include the linking logic into the configuration (→  144).
Options None
Digital output AD 1
Digital output AD 2
Factory setting None
Linking logic AD 1/2 (11181)
Navigation Expert → Diagnostics → Advanced diagnostics → Linking logic AD 1/2
Write access Maintenance
Prerequisite Only visible if the Advanced Diagnostics Block has been linked to the digital oputput of the
other Advanced Diagnostics Block via the Link AD 1/2 to parameter.
Descriptions Defines the linking logic between the two Advanced Diagnostics Blocks AD1 and AD2.

Table of Contents