The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
150 Endress+Hauser
Options AND
OR
Factory setting AND
Sample time 1/2 (11187)
Navigation Expert → Diagnostics → Advanced diagnostics → Sample time 1/2
Write access Maintenance
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Defines the scanning time in seconds for the calculation.
Input range 1 to 3 600 s
Factory setting 10 s
Calculation type 1/2 (11174)
Navigation Expert → Diagnostics → Advanced diagnostics → Calculation type 1/2
Write access Maintenance
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Defines, which quantity is derived from the assigned measured variable.
Options Off
Maximum
Minimum
Mean
Standard deviation
Difference Max. - Min.
Slope
Factory setting Off
Additional information The calculation is performed based on the defined Sample time. (I.e. the maximum,
minimum, mean, standard deviation, difference max.-min. or average slope within the
sample time are calculated.)
Check mode 1/2 (11175)