Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 151
Navigation Expert → Diagnostics → Advanced diagnostics → Check mode 1/2
Write access Maintenance
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Defines the check mode.
Options Off
Upper limit
Lower limit
In range
Out of range
Factory setting Off
Additional information If a calculation has been selected in the Calculation type parameter, the check does not
refer to the assigned measuring variable but to the quantity calculated from it.
Calculation unit 1/2 (11188)
Navigation Expert → Diagnostics → Advanced diagnostics → Calculation unit 1/2
Write access Operator
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Defines the unit for the selected Calculation type.
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Upper limit 1/2 (11182)
Navigation Expert → Diagnostics → Advanced diagnostics → Upper limit 1/2
Write access Maintenance
Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
Upper limit
In range
Out of range