The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
40 Endress+Hauser
Factory setting Silo
Additional information Depending on the Bin type parameter, the parameters Max. filling speed solid and Max.
draining speed solid are preset, among others.
Max. filling speed liquid (1212)
Navigation Expert → Sensor → Max. filling speed liquid
Write access Maintenance
Prerequisite Medium type = Liquid
Description Select expected maximum filling speed
Options Slow < 1cm (0.4in)/min
Medium < 10cm (4in)/min
Standard < 1m (40in)/min
Fast < 2m (80in) /min
Very fast > 2m (80in) /min
No filter / test
Factory setting Standard < 1m (40in)/min
Max. draining speed liquid (1202)
Navigation Expert → Sensor → Max. draining speed liquid
Write access Maintenance
Prerequisite Medium type = Liquid
Description Select expected maximum draining speed
Options Slow < 1cm (0.4in)/min
Medium < 10cm (4in)/min
Standard < 1m (40in)/min
Fast < 2m (80in) /min
Very fast > 2m (80in) /min
No filter / test
Factory setting Standard < 1m (40in)/min
Max. filling speed solid (1214)
Navigation Expert → Sensor → Max. filling speed solid