Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 41
Write access Maintenance
Prerequisite Medium type = Solid
Description Select maximum expected filling speed.
Options • Very slow < 0.5m (1.6ft) /h
• Slow < 1 m (3.3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test
Factory setting Standard < 2m (6,5ft) /h
Additional information The Max. filling speed solid parameter must be set according to the actual process
velocity.
Max. draining speed solid (1213)
Navigation Expert → Sensor → Max. draining speed solid
Write access Maintenance
Prerequisite Medium type = Solid
Description Select maximum expected draining speed.
Options • Very slow < 0.5m (1.6ft) /h
• Slow < 1 m (3.3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test
Factory setting Standard < 2m (6,5ft) /h
Additional information The Max. draining speed solid parameter must be set according to the actual process
velocity.
Advanced process conditions (1177)
Navigation Expert → Sensor → Advanced process conditions
Write access Maintenance
Description Defines additional process conditions (if necessary)