The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
42 Endress+Hauser
Options • None
• Weak signal
• Many obstacles
• Small tanks (< 1m/3ft)
• Changing DC values
• Foam (> 5cm/0.16ft)
Factory setting None
Additional information • Weak signal
Increases the sensitivity of the device in case of weak signals.
• Many obstacles
Can improve the behavior of the device in case of many obstacles in a silo if strongly
damping media (e.g. flour) are measured.
• Small tanks (< 1m/3ft)
Can improve the near-range measurement in small vessels.
• Changing DC values
Adjusts the signal evaluation of the device to strongly changing DC values of the
measured medium.
• Foam (> 5cm/0.16ft)
Adjusts the signal evaluation of the device to conditions with foam > 5 cm (1.6 in).
Application parameter (1126)
Navigation Expert → Sensor → Application parameter
Write access Read-only parameter
Description Indicates whether parameters have been changed after the basic setup.
Display options • Changed
• Not changed
Additional information Indicates whether a setting which depends on the application parameters (e.g. "Process
property", Advanced process conditions", "Tank type" and "Pipe diameter") has been changed
after the basic setup.
• Changed
Parameters have been changed. The device is no longer in the state defined by the
application parameters.
• Not changed
There have been no changes. The device is still in the state defined by the application
parameters.