Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 63
Additional information For Table mode = Manual: Level is a writable parameter.
For Table mode = Semi-automatic: Level is a read-only parameter.
Customer value (2384)
Navigation Expert → Sensor → Linearization → Customer value
Write access Maintenance
Prerequisite • Only visible for Linearization type = Table
• Only visible via operating tool (e.g. FieldCare), but not on the local display module.
Description Specification of the linearized value of the respective linearization point.
Input range -3,0 x 10
38
... +3,0 x 10
38
Factory setting 0
Activate table (2304)
Navigation Expert → Sensor → Linearization → Activate table
Write access Maintenance
Prerequisite Only visible if the "Table" linearization type has been selected.
Description Enables or disables the linearization table.
Options • Disable
A linearization is not calculated. If the Linearization type parameter has been set to
Table, the error message F435 is generated.
• Enable
The measured value is linearized according to the table before being sent to the output.
Factory setting Disable
Additional information When editing the table, this parameter is automatically reset to the Disable option. After
finishing the editing procedure it must be set to the Enable option again.