The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
62 Endress+Hauser
Additional information Conditions the linearization table must meet:
• The table may consist of up to 32 pairs of values "Level - Linearized Value".
• The table must be monotonic (monotonically increasing or decreasing).
• The first linearization point must refer to the minimum level.
• The last linearization point must refer to the maximum level.
Entering the table
• Via FieldCare: The table points may be entered via the parameters Table number,
Level and Customer value. As an alternative, the graphical table editor can be
used: Device Operation → Device Functions → Additional Functions →Linearization
(Online/Offline)
• Via the local display module: Access the graphical table editor by the Edit table
option. The table is dispayed on the display module and can be edited row by row.
The factory setting for the level unit is "%". If you want to enter the linearization table
in physical units, a suitable level unit has to be selected beforehand in the Expert →
Sensor → Level → Level unit parameter.
Table number (2370)
Navigation Expert → Sensor → Linearization → Table number
Write access Maintenance
Prerequisite • Only visible for Linearization type = Table
• Only visible via operating tool (e.g. FieldCare), but not on the local display module.
Description Number of the table point which will be defined by the next two parameters (Level and
Cusotmer value).
Input range 1 to 32
Factory setting 1
Level (2383/2389)
Navigation Expert → Sensor → Linearization → Level
Write access • For Table mode = Semiautomatic: Maintenance
• For Table mode = Manual: Read-only parameter
Prerequisite • Only visible for Linearization type = Table
• Only visible via operating tool (e.g. FieldCare), but not on the local display module.
Description Definition or display of the (unlinearized) level of the respective linearization point.
Input range Depending on the parametrized measuring range. See the parameters Empty
calibration(→ 47) and Full calibration(→ 48).
Factory setting 0