Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 61
Prerequisites Only visible if one of the following linearization types has been selected:
Pyramid bottom
Conical bottom
Angled bottom
Description Definition of the intermediate height H
0%
H
A0013264
Input range 0 to 200 m (0 to 656 ft)
Factory setting 0 m (0 ft)
Additional information The value must be specified in the selected distance unit (→  38).
Table mode (2303)
Navigation Expert → Sensor → Linearization → Table mode
Write access Maintenance
Prerequisite Only visible if the "Table" linearization type has been selected.
Description Defines the method used to enter linearization points into the table.
Options Manual
The level and the associated linearized value are entered manually for each linearization
point.
Semi-automatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
Clear table
Deletes the existing linearization table.
Sort table
Rearranges the linerization points into an ascending order.
Factory setting Manual