Proline Promag 10 Wiring
Endress+Hauser 37
3.2.2 Promag H connecting cable
Connecting cable termination
Terminate the signal and coil current cables as shown in the figure below (Detail A).
Fit the fine-wire cores with cable end ferrules (Detail B).
Signal cable termination
Make sure that the cable end ferrules do not touch the wire shields on the sensor side! Minimum
distance = 1 mm (0.04 in), exception "GND" = green cable.
Coil current cable termination
Insulate one core of the three-core cable at the level of the core reinforcement; you only require
two cores for the connection.
Sensor Transmitter
mm (inch)
a = 80 (3.15")
b = 15 (0.59")
c = 17 (0.67")
d = 8 (0.31")
e = 1 (0.04")
a0008985
mm (inch)
a = 80 (3.15")
b = 50 (1.97")
c = 17 (0.67")
d = 8 (0.31")
m
= Cable end ferrules, red, 1.0 mm (0.04");
n
= Cable end ferrules, white, 0.5 mm (0.02")
Sensor Transmitter
mm (inch)
a = 70 (2.76")
b = 40 (1.57")
c = 15 (0.59")
d = 8 (0.31")
a0008986
mm (inch)
a = 70 (2.76")
b = 50 (1.97")
c = 10 (0.39")
d = 8 (0.31")
m
= Cable end ferrules, red, 1.0 mm (0.04");
n
= Cable end ferrules, white, 0.5 mm (0.02")