Fix the cable run or route it in an armored conduit.
Cable movements can influence the measuring signal especially in the case of low fluid
conductivities.
Route the cable well clear of electrical machines and switching elements.
Ensure potential equalization between sensor and transmitter (→  20).
Connection examples
Current output 4-20 mA HART
4
4...20 mA
+
5
2
1
3
6
+
_
A0016800
 4 Connection example for 4-20 mA HART current output (active)
1 Automation system with current input (e.g. PLC)
2 Cable shield, observe cable specifications (→  22)
3 Connection for HART operating devices (→  84)
4 Resistor for HART communication (≥ 250 Ω): observe maximum load (→  8)
5 Analog display unit: observe maximum load (→  8)
6 Transmitter
Current output 4-20 mA
0/4...20 mA
+
2
1
3
+
_
A0017162
 5 Connection example for 0-20 mA current output (active) and 4-20 mA current output (active)
1 Automation system with current input (e.g. PLC)
2 Analog display unit: observe maximum load (→  8)
3 Transmitter