• Fix the cable run or route it in an armored conduit.
Cable movements can influence the measuring signal especially in the case of low fluid
conductivities.
• Route the cable well clear of electrical machines and switching elements.
• Ensure potential equalization between sensor and transmitter (→ 20).
Connection examples
Current output 4-20 mA HART
A0016800
4 Connection example for 4-20 mA HART current output (active)
1 Automation system with current input (e.g. PLC)
2 Cable shield, observe cable specifications (→ 22)
3 Connection for HART operating devices (→ 84)
4 Resistor for HART communication (≥ 250 Ω): observe maximum load (→ 8)
5 Analog display unit: observe maximum load (→ 8)
6 Transmitter
Current output 4-20 mA
A0017162
5 Connection example for 0-20 mA current output (active) and 4-20 mA current output (active)
1 Automation system with current input (e.g. PLC)
2 Analog display unit: observe maximum load (→ 8)
3 Transmitter