Proline Promag W 400
Endress+Hauser 11
Operating tool
• Via digital communication:
HART protocol
• Via service interface
Plain text display With information on cause and remedial measures
Additional information on remote operation (→ 84)
Web browser
Plain text display With information on cause and remedial measures
Light emitting diodes (LED)
Status information Status indicated by various light emitting diodes
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
Low flow cut off
The switch points for low flow cut off are user-selectable.
Galvanic isolation
The following connections are galvanically isolated from each other:
• Inputs
• Outputs
• Power supply
Protocol-specific data HART
Manufacturer ID 0x11
Device type ID 0x67
HART protocol revision 6.0
Device description files
(DTM, DD)
Information and files under:
www.endress.com
HART load Min. 250 Ω
Dynamic variables The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Off
• Volume flow
• Mass flow
• Flow velocity
• Electronics temperature
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Mass flow
• Flow velocity
• Conductivity
• Electronics temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3