Proline Promag W 400
Endress+Hauser 35
Flange connection according to JIS B2220
10K
20K
-40
-20
0 20
40 60 80 100120140 160180 [°C]
0
10
20
30
[bar]
360 [°F]
0-40 100 200 300
[psi]
200
100
400
300
0
A0021183-EN
 25 Fixed flange 10K/20K, materials HII, S235JRG2 and 1.0425 (316L), DN 25 to 300 (1 to 12")
Pressure tightness
Liner: hard rubber
Nominal diameter Limit values for absolute pressure in [mbar] ([psi]) for fluid temperatures:
[mm] [in] +25 °C (+77 °F) +50 °C (+122 °F) +80 °C (+176 °F)
50…2000 2…78 0 (0) 0 (0) 0 (0)
Liner: polyurethane
Nominal diameter Limit values for absolute pressure in [mbar] ([psi]) for fluid temperatures:
[mm] [in] +25 °C (+77 °F) +50 °C (+122 °F)
25…1200 1…48 0 (0) 0 (0)
Flow limit
The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The
optimum flow velocity is between 2 to 3 m/s (6.56 to 9.84 ft/s). Also match the velocity of flow (v)
to the physical properties of the fluid:
v < 2 m/s (6.56 ft/s): for abrasive fluids (e.g. potter's clay, lime milk, ore slurry)
v > 2 m/s (6.56 ft/s): for fluids producing buildup (e.g. wastewater sludges)
For an overview of the measuring range full scale values, see the "Measuring range" section
(→  6)
For custody transfer, the applicable approval determines the permitted measuring range.
Pressure loss
No pressure loss occurs if the sensor is installed in a pipe with the same nominal diameter.
Pressure losses for configurations incorporating adapters according to DIN EN 545 (→  28)
System pressure
Never install the sensor on the pump suction side in order to avoid the risk of low pressure, and
thus damage to the liner.
Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps are used.
For information on the liner's resistance to partial vacuum (→  35)
For information on the measuring system's resistance to vibration and shock (→  31),
(→  31)