Wireless TimeClock Configuration Guide 11
Configuration Parameter
The Configuration Parameter number specifies which controller setting is to
be temporarily altered. The table below describes the defined Config Param
numbers.
Config
Param
Setting Description Value Description
1 Partial-ON Enable Yes or No
2 Partial-ON Level Percentage: 0 to 100%
3 Partial-OFF Enable Yes or No
4 Partial-OFF Level
Percentage: 0 to 100%
(20% default)
5 Timed Switch On Duration
Timer setting in seconds
(e.g.: 00600 for 10 min)
6 Daylighting Manual Override Enable Yes or No
7 Daylighting Manual Override Timeout
Timer setting in seconds
(e.g.: 00600 for 10 min)
8 Maximum Dimming Level Percentage
9 Occupancy Timer Timeout
Timer setting in seconds
(e.g.: 00900 for 15 min)
10 to 99 Unspecified parameters TBA future development
Note: To learn more about the controller settings that can be mod-
ified, and how they affect controller behavior, contact your Echoflex
support representative.