Wireless TimeClock Configuration Guide 19
Manual DST Dates
DST Start Date
Month:: March
Day of week: Sunday
Occurence: Second
DST End Date
Month: November
Day of week: Sunday
Occurence: First
Set custom or manual Daylight Saving Time dates
as needed.
1. Select Manual DST Dates from the
TimeClock Settings menu, and press [Enter]
to select. The manual DST Dates menu
displays the current DST start and end
dates.
2. Press [Enter] to set new start and end dates.
3. Press [Up] or [Down] to scroll, and [Enter] to set the DST Start Date
settings: Month, Day of Week, and Occurrence.
4. Press [Up] or [Down] to scroll, and [Enter] to set the DST End Date
settings: Month, Day of Week, and Occurrence.
Sweep Interval
The Sweep feature ensures that an event setting remains in effecta rein-
forcement in case a manual setting overrides the event. The Sweep Interval
defines the frequency that the event settings are reset, maximum 360
minutes. For example, if the Sweep Duration is two hours and the Sweep
Interval is 10minutes, a total of 12 Sweeps would be executed after the
scheduled event has occurred.
For the Sweep Interval to be in effect, the scheduled event must have
Sweep enabled with a set duration. The Sweep feature is available for
Action types Scene, ON to Level, and OFF. See Define an ON to Level Action
on page13 for an example.
1. Select Sweep Interval from the TimeClock Settings menu, and press
[Enter] to modify.
2. Press [Up] or [Down] to scroll to the target Sweep Interval frequency,
and press [Enter] to select.
Timed Hold
The Timed Hold feature sets the duration of the Hold that suspends all
scheduled events. Timed Hold is set to 120minutes by factory default to
comply with energy conservation standards. The duration can be set to any
value from 10 to 360 minutes, in 10-minute increments.
1. Select Timed Hold from the TimeClock Settings menu, and press
[Enter] to modify.
2. Press [Up] or [Down] to scroll to the target Timed Hold duration, and
press [Enter] to select.