EVCO S.p.A.
EVBOX1 | Installation guide ver. 2.0 | Code 144BOX1E204
page 59 of 100
PARAM. MIN. MAX. M.U.
EVB1204
EVB1214
EVB1206
EVB1216
EVB1226
EVB1236
EVB1246
EVB1256
TEMPERATURE ALARMS
A0 0 1 - - - - 0 0 0 0 0 0 0 0
temperature associated with the minimum temperature
alarm (code “AL)
0
=
room temperature or CPT temperature
1
=
evaporator temperature (20)
A1 -99.0 99.0
°C/°F
(1)
-10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0
temperature below that at which the minimum
temperature alarm is activated (code AL”); see also A0,
A2 and A11
A2 0 2 - - - - 0 0 0 0 0 0 0 0
type of minimum temperature alarm (code “AL)
0
=
alarm absent
1
=
relative to working set-point (that is “working set-
point - A1”; consider A1 without sign)
2
=
absolute (that is A1)
A4 -99.0 99.0
°C/°F
(1)
10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0
temperature higher than that at which the maximum
temperature alarm is activated (code AH”); see also A5
and A11
A5 0 2 - - - - 0 0 0 0 0 0 0 0
type of maximum temperature alarm (code “AH”)
0
=
alarm absent
1
=
relative to working set-point (that is “working set-
point + A4”; consider A1 without sign)
2
=
absolute (that is A4)
A6 0 240 min 120 120 120 120 120 120 120 120
delay in maximum temperature alarm (code AH”) after
the device is switched on (8)