EVBOX1 | Installation guide ver. 2.0 | Code 144BOX1E204
page 60 of 100
A7 0 240 min 15 15 15 15 15 15 15 15 temperature alarm delay (code “AL” and codeAH”)
A8 0 240 min 15 15 15 15 15 15 15 15
delay in maximum temperature alarm (code AH”) from
the conclusion of evaporator fan standstill (21)
A9 0 240 min 15 15 15 15 15 15 15 15
delay in maximum temperature alarm (code AH”)
following the deactivation of the door micro switch input
(22)
A10 0 240 min 1
not
avail.
1
not
avail.
1
not
avail.
1
duration of a power cut such to cause the power cut alarm
to be memorised (code “PF”)
A11 0.1 (5) 15.0
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 differential of parameters A1 and A4
A12 0 2 - - - -
not
avail.
1
not
avail.
1
not
avail.
1
not
avail.
1
type of power supply cut-off alarm signal (codePF”)
0
=
alarm will be signalled by the “HACCP” LED
1
=
alarm will be signalled by the PF code, the
buzzer and the “HACCP” LED
2
=
alarm will be signalled by the PF
code, buzzer
(as long as cut-off duration exceeds time A10)
and by the “HACCP” LED