EVCO S.p.A.
EVBOX1 | Installation guide ver. 2.0 | Code 144BOX1E204
page 63 of 100
F8 0.1 (5) 15.0
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 F1 differential
F9 0 240 s 0 0 0 0 0 0 0 0
delay in the switching off of evaporator fan following the
switching off of the compressor (only if F0 = 2, 4 and 5)
F11 0.0 99.0
°C/°F
(1)
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
temperature of the condenser above which the condenser
fan is switched on (“F11 + 2,0 °C/4 °F, only if u1 and/or
u11 = 6) (29) (30)
F12 0 240 s 30 30 30 30 30 30 30 30
delay in the switching off of condenser fan following the
switching off of the compressor (only if u1 and/or u11 =
6)
F13 0 240 sx10 30 30 30 30 30 30 30 30
duration of evaporator fan switch off during “energy
saving” function, see also F14, i10, H01... H14 (only if F0
= 1, 2, 3 or 4)
F14 0 240 sx10 30 30 30 30 30 30 30 30
duration of evaporator fan switch on during “energy
saving” function, see also F13, i10, H01... H14 (only if F0
= 1, 2, 3 or 4)