EVER UPS SINLINE RT / RT XL series instruction manual
2017-04-26 12:41
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
26
The description of options available from the CONFIGURATION submenu is
presented below.
UPS 1/2
Description: Parameters of the UPS unit
Type: Readout/Saving
Parameters:
Output Voltage
configuration of the UPS unit's output voltage when in back-
up mode (battery operation)
MinOutputVolt.
configuration of the UPS unit's output voltage bottom
threshold If the voltage drops below this value, the UPS goes
into the back-up mode or the AVR is activated to increase the
voltage
MaxOutputVolt.
configuration of the UPS unit's output voltage upper
threshold If the voltage rises above this value, the UPS goes
into the back-up mode or the AVR is activated to decrease
the voltage
MinOutputFreq.
configuration of the UPS unit's output frequency bottom
threshold
MaxOutputFreq.
configuration of the UPS unit's output frequency upper
threshold
Ovrld.Clr.Thr.
setting the percentage of load at which the UPS unit stops
indicating overload
STB Charge
setting the minimum battery charging level that needs to be
achieved to enable the UPS unit to start after the battery is
discharged and after the voltage in the mains is available
again (battery charging resumes)
Number of EBMs
setting the number of external battery modules connected
to the UPS If there are no external battery modules, set the
value to 0. CAUTION! Setting a different value may damage
the UPS unit's battery. The option is available in SINLINE RT
XL UPS units.
Output Control
activating / deactivating a group of output sockets (white)
The option can be selected in MAINS and BACK-UP mode.
The option is available in SINLINE RT XL UPS units.