EVER UPS SINLINE RT / RT XL series instruction manual
Pomoc Techniczna, tel.: +48 61 6500 400
WARNING EPO circuit must be a separate circuit
and it is forbidden to connect it with other installations.
For more information about the card see the EXPANSION CARDS chapter.
INSTALLATION
INSTALLING THE UPS UNIT
After unpacking, please inspect the device for damages. The UPS should only be
used in rooms where the dust, temperature, and humidity levels are within the
device's specifications.
Appropriate cooling conditions must be ensured for the UPS to work properly. For
this reason, the distance between the UPS and other objects should not be less than
20 cm.
The mains socket the UPS is to be connected to, should be located near the unit
(maximum distance – 1.8 m) and should be easily accessible.
CAUTION! No extension cords should be used for connecting the UPS
unit.
CAUTION! Installing a UPS unit in proximity of flammable materials or
substances is strictly prohibited!
Due to the type and placement of the fuses in the UPS, it is recommended that the
protection systems in the building's electric system be used as one of protection
levels. This is necessary to ensure short circuit protection for the UPS. The
UPS may only be connected to a ~230V mains socket equipped with a
grounding bolt.
All SINLINE RT / SINLINE RT XL series UPS units were designed to operate as free
standing units (tower versions) and for installation in 19" rack cabinets (rack
versions). Follow the instructions below to prepare the device to operate as a free
standing or cabinet-mounted unit.