EVER UPS SINLINE RT / RT XL series instruction manual
Pomoc Techniczna, tel.: +48 61 6500 400
The UPS is in
STOP mode and
is logically on (
UPS active)
The battery is discharged and waits until
minimal charge is reached. No power
supply.
Once the power supply is back and the
battery reaches the minimal charge level, the
UPS goes into mains mode.
Increasing AVR
interlock (Incr.
AVR interlock)
Excessively high value of minimal output
voltage is configured.
Change the value of the minimum and
the maximum output voltage
(CONFIGURATION, UPS).
Decreasing AVR
interlock (Decr.
AVR interlock)
Excessively low value of maximal output
voltage is configured.
Change the value of the minimum and
the maximum output voltage
(CONFIGURATION, UPS).
The UPS unit has detected improper
output impedance level.
Disconnect all receivers from the UPS unit.
Delete the fault (CONTROL; Clear fault).
Make sure that the short circuit is removed
before switching the device back on.
Disconnect some receivers from the UPS
unit. The alarm is deactivated once that
issue is solved.
Permissible temperature of the battery or
inverter is exceeded.
Wait until the UPS unit cools down. Ensure
free air circulation around the UPS unit.
Restart the UPS unit. Restart the UPS unit.
Check the EPO connector condition and set
the trigger to inactive position (trigger's
default state), and then delete the
emergency flag signalization (Control; Clear
fault). Restart the UPS.