lead. The summary leakage current may trigger protective devices (RCD) and
result in disconnecting power to the loads.
When connecting and disconnecting signal cables, all actions should be
performed with one hand only (if feasible). This is to avoid electric shock when
touching two surfaces with different electrical potentials.
Leads connected to the UPS's output should not be longer than 10 m, in order to
maintain conformance with the EMC directive for products sold in Europe.
Connecting leads should be placed so that people walking over them will not step
or trip on them.
An emergency power-off button (EPO), dedicated to the UPS system, should be
installed in the building's electrical system. This is to allow disconnecting, in
emergency, the UPS unit from the connected loads regardless of the mode in
which the UPS is operating.
To minimize the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected
overcurrent protection. Additionally, the breaker should feature at least a 3 mm
insulating air gap.
C) Operation of the UPS unit
Health and Safety regulations and guidelines specified in the UPS unit operating
manual must be observed when handling and operating the UPS unit.
All these instructions must be executed step by step. If any problems emerge
when executing the instructions given in this document, please contact EVER
service support (www.ever.eu).
Never disconnect the grounding at the UPS unit or at the terminals of the
building's electrical system, as this will disable the UPS unit's protective
grounding.
There may be voltage on the UPS's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in
the device's internal batteries).
Liquids and foreign bodies must not be allowed to penetrate the UPS casing.
WARNING: This is a C2 category UPS. If installed in residential environment, this
product may interfere with radio signals, which may require additional precautions
to be employed by the user.