Extreme Networks ExtremeSwitching SLX 9540 - Installing the Universal Four-Post Rack Kit (XEN-R000296)

Extreme Networks ExtremeSwitching SLX 9540
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Tighten all the 8-32 x 5/16-in. screws to a torque of 15 in-lb (17 cm-kg).
FIGURE 18 Attaching the rear brackets to the device
1. Screws, 8-32 x 5/16-in., panhead Phillips
Installing the Universal Four-Post Rack Kit (XEN-
R000296)
Use the following instructions to install 1U and 2U devices in EIA racks that are between L-12.7 to 81.28 cm deep (L-5.0 to 32.0 in.),
where L is the chassis depth, using the Universal Four-Post Rack Kit (XEN-R000296).
There are two ways you can mount the device in a four-post rack:
With the port side ush with the front posts.
With the nonport side ush with the rear posts in a recessed position. A recessed position allows a more gradual bend in the
ber-optic cables connected to the switch and less interference in the aisle at the front of the rack.
TABLE 9 Space requirements
Chassis with port-side
side vents
Notes Chassis depth Minimum rack depth Maximum rack depth
No Applicable to port-side and nonport-side ush
mounts.
L L-12.7 cm (L-5 in.) 81.28 cm (32 in.)
Yes Applicable to port-side ush mounts. L L-12.7 cm (L-5 in.) 81.28 cm (32 in.)
Yes Applicable to nonport-side ush mounts. L L 81.28 cm (32 in.)
Installing the Universal Four-Post Rack Kit (XEN-R000296)
ExtremeSwitching SLX 9540 Hardware Installation Guide
9036360-00 Rev AB 39