IN1804 Seamless Scaling Switchers • SIS Configuration and Control 54
X2@
= Test patterns
0 = Off (default)
1 = Crop
2 = Alternating pixels
3 = Crosshatch
4 = Color Bars
5 = Grayscale
6 = Audio test — Crop pattern with orbiting text AUDIO
TEST and outputting pink noise at LPCM-2Ch, 48 Hz,
24-bit.
X2^
= Input presets
1 through 128
Response is three digits, padded with zeros.
X2*
= Output sync or OSD menu
timeout
Number of seconds before output sync or the OSD menu
times out.
1 through 500 seconds, in 1-second increments
0 = Output sync is instantly disabled with no active video
from the selected input (not allowed for MDUR
command).
60 = Default for the MDUR command.
501 = Output sync never times out (default for SSAV
command).
X2(
= Front Panel Lockout (executive)
mode status
0 = Off or disabled (front panel controls fully accessible)
(default).
1 = Mode 1 — Complete front panel lockout
2 = Mode 2 — Input switching only
X3)
= Auto-input switch mode
0 =
Disabled — Manual switching (default)
1 =
User-defined priority mode —
The switcher selects
the input to which the user assigns priority. If no
priority is assigned, the switcher selects the active
priority input with the lowest number.
2 =
Last connected mode —
The switcher selects the
most recently applied input, and retains a history of
the order in which active inputs are connected to the
unit.
If an active input is removed, the switcher switches to
the most recently prioritized input.
X3!
= Auto-input switching priority
Input number for input switching priority.
1 = Input 1
2 = Input 2
3 = Input 3
4 = Input 4
X3@
= Auto-input switch timeout Number of seconds without video that elapse before
switching to the previous input.
1 through 500 in 1-second increments
3 = Default
0 =
Immediately switch to most recent input if the
current input is removed.
X3#
= Number of characters Number of characters in the command being sent.