MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
10
OPTIONAL MODULES
CT-1K City Tie Board (MPC-6000 / MPC-7000 / RND-2)
The Faraday CT-1K city tie board provides local energy and polarity reversal connections. The
polarity reversal connections provide a trouble circuit and an alarm circuit with optional trouble
output. The CT-1K mounts on the MPC6-MB, MPC6-MB2 or MPC7-MB (Cannot be used in
conjunction with a DACT Board).
MPC-DACT Board (MPC-6000 / MPC-7000 / RND-2)
The Faraday MPC-DACT Digital Alarm Communication Transmitter board will send control unit
status data to a remote receiving station. The MPC-DACT mounts the MPC6-MB, MPC6-MB2
or MPC7-MB (Cannot be used in conjunction with the City Tie Board).
NPE-1 Transformer Assembly (MPC-6000 / MPC-7000)
The Faraday NPE-1 optional transformer assembly provides an additional 3 amps of NAC
power. The transformer mounts in the cabinet above the two transformers that come standard
with the MPC-6000 / MPC-7000. A maximum of one optional NPE-1 is allowed per system.
NEM-1 NAC Expansion Board (MPC-7000)
The NEM-1 NAC Expansion Board has eight independent Class B (Style Y) notification
appliance circuits (NACs). Pairs of NACs can be combined for Class A (Style Z) operation.
This reduces the number of NACs to four. Each circuit can be selected to give continuous
output or one of five sounding patterns. There is also a system coder capable of zone-coded
operation.
All of the NACs are power limited and support synchronization of listed devices via the
Faraday SYNC Protocol. If a NEM-1 is installed in an MPC-7000 panel, its NACs are
synchronized in sets of 4 as follows:
NAC1, NAC2, NAC3 and NAC4 are synchronized with each other.
NAC5, NAC6, NAC7 and NAC8 are synchronized with each other.
NAC9, NAC10, NAC11 and NAC12 are synchronized with each other.
A maximum of one NEM-1 NAC Expander board can be installed per MPC-7000 panel.
LEM-1 Loop Expander Board (MPC-7000)
The LEM-1 has circuitry for the addition of an additional two FDLC Loop Driver boards to a
MPC-7000 panel. (FDLC Loop Driver Boards are not included). A maximum of one Loop
Expander Board is allowed per MPC-7000 system.
FDLC Loop Driver Board (MPC-7000)
The FDLC has one addressable device circuit that is programmed for connection to Faraday
addressable devices using the X1. The circuit has the capacity for 252 addresses. A maximum
of four FDLC boards per MPC-7000 panel is allowed. (Loops 3 and 4 require a LEM-1 Loop
Expander Board.)
HBC-1 Battery Charger (MPC-7000)
The HBC-1 is an optional battery charger to increase the charging capacity of the MPC-7000
up to 100AH lead acid batteries.