MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
82
APPENDIX-K: DIAGNOSTIC LEDS
The LEDs on the following boards are used for diagnostic purposes only.
MPC6-MB / MPC6-MB2
DS3 ON, indicates Low battery voltage or No battery detected.
DS2 ON, indicates High Battery voltage detected.
DS4 ON, indicates panel detected a ground fault condition.
DS16 ON, indicates defective battery charger circuit.
DS1 OFF, indicates panel detected an AC Failure.
DS12 ON, indicates that NAC1 is active.
DS13 ON, indicates that NAC2 is active.
DS14 ON, indicates that NAC3 is active.
DS15 ON, indicates that NAC4 is active.
DS5 ON, indicates Relay #1 is activated.
DS6 ON, indicates Relay #2 is activated.
DS7 ON, indicates Relay #3 is activated.
DS8 ON, indicates Relay #4 is activated.
DS9 ON, indicates voltage is OFF on TB9-R terminal.
DS10, DS11 flashing indicates that I2C communication line is active.