MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
51
X1 Addressable Device Circuit(s)
These devices are polled by the control unit every few seconds and input or output functions
communicated to determine device status or function. The control unit monitors all device
addresses for alarm and trouble conditions.
Loop Circuit 1
Addressable
MPC-6000 - X1 ADDRESSABLE DEVICE CIRCUIT
Loop Circuit 2
Addressable
Loop Circuit 1
Addressable
OUT
IN
Circuit (IN & OUT)
Serial Interface
MPC-7000 - X1 ADDRESSABLE DEVICE CIRCUIT
Addressable Device Circuit
Style 4 (Class B) or Style 6
(Class A) Operation
24VDC nominal
(31VDC max.) filtered
0.375 Amp. Max.
Wire Resistance-50 ohms max
(See Appendix A, Line
Resistance Graph)
Supervised, Power Limited
See Appendix B for Compatible
Devices
Addressable Device Circuits
Style 4 (Class B) or Style 6 (Class A) Operation
24VDC nominal, filtered (31VDC max.)
0.375 Amp. Max.
Wire Resistance-50 ohms max.
(See Appendix A, Line Resistance Graph)
Supervised, Power Limited
See Appendix B for Compatible Devices