MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
20
City Tie (Optional City Tie Board P/N CT-1K)
CA Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation
Not power limited
Supervised by receiver
Voltage: 24 VDC nominal (31 VDC max.) filtered
Current: 0.020A maximum (normal or trouble)
Current: 0.025A maximum (shorted)
Ripple: 1.5 VAC maximum, 120Hz
CT Reverse Polarity: Programmable for Trouble or Supervisory or both
Not power limited
Supervised by receiver
Voltage: 24 VDC nominal (31 VDC max.) filtered
Current: 0.020A maximum (normal or alarm)
Current: 0.025A maximum (shorted)
Ripple: 1.5 VAC maximum, 120Hz
LE Local Energy
Not power limited
Supervised for open by control unit
Voltage: 24 VDC nominal (31 VDC max.) filtered
Standby Current: 0.007A maximum
Alarm Current: 0.400A maximum
Ripple: 1.5 VAC maximum, 120Hz
Maximum wire loop resistance: 30 ohms
Trip coil impedance: 14.5 ohms
DACT Circuit (Optional DACT Board MPC-DACT)
Power limited
Supervised for short or open circuit
Maximum Voltage: 60 VDC
Maximum Current (shorted): 0.100A
Additional Transformer (Optional Transformer Sub-assembly NPE-1)
Provides an additional 3.0A of NAC power (max. 1 per panel)