MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
70
D. Validation and Warning
Warning/Error Messages Condition
Address 1xxx-1 bad input usage Loop 1 address xxx requires valid input usage.
Address out of range 1001-4353 Device being programmed is out of range.
City Tie required in auxiliary system No City Tie installed in Auxiliary system type.
Counting Zone Group xxx: too few points Counting Zone at Input Group xxx has less devices than
required.
Dact Account x bad PN DACT account x has a bad phone number.
Dact alm restore event not rept An installed DACT must have alarm and alarm restore
configured on account 1.
Detector 1xxx-1: Alarm input not in a valid
group
Loop 1 addresss xxx needs to be programmed to valid
input group.
Detector 1xxx-1: Fire input doesn’t activate
an audible NAC
Fire input group the device belongs to is not properly
configured.
Detector 1xxx: ASD with alarm verify is not a
Duct detector
Configured an 8713 FireSmart detector for “Office” and for
“Alarm Verify”.
Detector 1xxx enabled but no type selected Loop 1 address xxx requires device type configuration.
General alarm group fails to activate an
audible NAC
The general alarm must have at least 1 output zone
selected that is configured with at least one NAC circuit.
Warning: 1xxx-1: doesn’t activate an audible
NAC in PAS/Pre-signal
No output zone selected on the NAC, no output group
selected for input zone.
Warning: City tie not allowed in local system A City Tie is programmed and set up for a local system.
Warning: Dact not allowed in local system A DACT is programmed and set up for a local system.
Warning: No zone selected for group xxx Input group xxx has no output zone selected or input group
is not activated.