MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
89
Global Accept
This option can only be configured in MPC-6000/-7000 networked panels. There are two
programming options for Global Accept, “Yes” and “No”.
• Setting this option to “Yes” allows a Networked panel (MPC-6000/-7000) to be silenced,
acknowledged and reset from the RND-2.
• Setting this option to “No” requires independent silence, acknowledge and reset at the
local panel.
Global Send
Setting this option to “Yes” at the RND-2 allows the RND-2 to activate General Alarm, Alert,
Drill and Recall from the RND-2 to the networked panels. Setting this option to “No” disables
this feature.