Possible reason for error
The expansion card cannot communicate via the
encoder's bus
• Communication with expansion board is not possible
• No expansion board pluged in
• CAN Connection interrupted (Broken cable or no supply voltage for extension
board)
• Check that the RUN LED flashes
Software version incompatible
The software version of the RFUxIO expansion board is not up-to-date or
incompatible with the software of the door controller.
RFUxIO is plugged in but not activated. Set Parameter P.800 = 8
Time-out with protocol transmission by ASC1
• Interface connection faulty or interrupted
• defective hardware or strongly interfered surrounding
• use shielded control cable
Wrong Test of input 1 of the mobile unit
TST FSx
• Input 1 of the mobile unit was tested as faulty
• The device connected to the input does not work
• The mobile unit is defective
Wrong Test of input 2 of the mobile unit
TST FSx
• Input 2 of the mobile unit was tested wrong
• The device which is connected to the input does not work correctly
• The mobile unit is defective
Wrong Test of input 3 of the mobile unit
TST FSx
• Input 3 of the mobile unit was tested as faulty
• The device connected to the input does not work
• The mobile unit is defective
Wrong Test of input 4 of the mobile unit
TST FSx
• Input 4 of the mobile unit was tested as faulty
• The device connected to the input does not work
• The mobile unit is defective
Wrong Test of input A of the stationary unit TST FSx
• Input A of the stationary unit was tested wrong
• The device which is connected to the input does not work correct
• The stationary unit is defective
Wrong Test of input B of the stationary unit TST FSx
• Input B of the stationary unit was tested wrong
• The device which is connected to the input does not work correct
• The stationary unit is defective
Wrong Test of input C of the stationary unit TST FSx
• Input C of the stationary unit was tested wrong
• The device which is connected to the input does not work correct
• The stationary unit is defective