Positioning
All series units are designed for outside installation. To ensure correct installation:
. Make sure the support surface is perfectly level and that it can take the weight of the unit. It is advisable to create a base of
suitable size for the unit. This precaution is indispensable when placing the unit on unstable ground (various types of ground,
gardens, etc.). The units transmit a low level of vibrations to the ground: in any case it is advisable to place a strip of rigid rubber
between the base frame and the support surface. Whenever more efficient insulation is required, it is advisable to use vibration-
damping spring supports. Do not place the units near private offices, bedrooms or areas where noise levels must be low. It is also
inadvisable to install the unit in narrow or confined spaces, in order to avoid reverberation.
. Pay attention to its orientation and exposure to sun radiation: insofar as possible, the condensing coil should not be exposed
to direct sunlight. To avoid operating overtemperatures, do not place the unit on dark ground (e.g. tarred surfaces).
. Do not cover the unit with roofs or place it near plants (even if they only partially cover the unit), in order to reduce the
possibility of air recirculation.
. Respect the functional areas and make sure the place of installation is not subject to flooding.
. Position the unit so that is protected against any prevailing winds.
. Secure the unit to the ground.
Typical roof installation with frontal inlet and outlet
RECEIVING AND POSITIONING
Giunto
flessibile
Canale aria
di mandata
Canale aria
di ripresa
Presa
aria esterna
Soletta
di supporto
Nastro di
gomma rigido
Support
base
Rigid
rubber strip
Outdoor
air inlet
Return air duct
Air flow duct
Flexible joint