EasyManua.ls Logo

Ferroli RFA - Alarm Table

Ferroli RFA
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
CONTROL SYSTEM
Loads BLOCKED
Compressor circuit 1
Compressor circuit 2
Reverse cycle valve circuit 1
Reverse cycle valve circuit 2
Internal fan - Return air fan
Electrical heater coil
Gas heating module
Hot water coil 3 way valve
External fans circuit 1
External fans circuit 2
Outdoor air damper
CODE ALARM
RESET
(1)
RL2 RL1 RL2 RL3 RL4 RL5 RL6 RL7 TC1 TC2 AN3
E00 Remote ON-OFF A ID10 x x x x x x x x
E01
High pressure circuit 1Compressor ther-
mal cut-out circuit 1External fans thermal
cut-out circuit 1
M ID1 x
E02 Low pressure circuit 1Sequence meter AS (3) ID2 x x
E05 Outlet air low temperature AS (3) (2) AI2 x x x x
E06 Outlet air temperature probe fault A AI2 x x x x x x x
E07 Fluid probe fault circuit 1 A AI3 x x x x x x
E21
High pressure circuit 2Compressor ther-
mal cut-out circuit 2External fans thermal
cut-out circuit 2
M ID3 x x
E22 Low pressure circuit 2 AS (3) ID4 x x
E26 CO2 probe fault A AI5 x x x x x x x x
E27 Fluid probe fault circuit 2 A AI6 x x x x x
E40 Inlet air temperature probe fault A AI1 x x x x x x x x
E41 Filters differential pressure switch M ID6 x x x x x x x x
E42 Outside air temperature probe fault A AI4 x x x x x x x x
E43
Internal fan thermal cut-out Inlet fan ther-
mal cut-out
M ID5 x x x x x
E46 Inlet air high temperature A AI1 x x x x x x
E48 Inlet air humidity probe fault A AI7
E49 Outside air humidity probe fault A AI8
E63
Heaters thermal cut-outGas-fired heating
module alarm
M ID7 x
Alarm table
(1) A = automatic reset , M = manual reset , AS (x) = automatic until reaching x events per hour, then manual
(2) Manual reset can also be carried out by means of remote On-Off (ID10) or remote Cooling-Heating (ID11)

Table of Contents

Related product manuals