CONTROL SYSTEM
Label Description RW
Register address
Bit num-
ber
Lsb CPL EXP UM
Dec Hex
- Cooling set point RW 2049 0801 16 0 Y -1 °C
- Heating set point RW 2050 0802 16 0 Y -1 °C
H10
Enable heat pump RW 2060 080C 16 0 N 0 -
H49
Operating mode selection configuration RW 2099 0833 16 0 N 0 -
H67
Family serial address RW 2117 0845 16 0 N 0 -
H68
Device serial address RW 2118 0846 16 0 N 0 -
b01
Automatic operating mode hysteresis in cooling RW 2168 0878 16 0 N -1 °C
b02
Automatic operating mode hysteresis in heating RW 2169 0879 16 0 N -1 °C
r07
Antifreeze heaters set point in heating RW 2210 08A2 16 0 Y 0 °C
r08
Antifreeze heaters set point in cooling RW 2211 08A3 16 0 Y 0 °C
r13
Heat pump shut-down set point RW 2216 08A8 16 0 Y 0 °C
r15
Enable heaters in heating RW 2218 08AA 16 0 N 0 -
r16
Enable heaters in dehumidification RW 2219 08AB 16 0 N 0 -
L01
Enable free cooling RW 2252 08CC 16 0 N 0 -
L07
Shutter min. opening RW 2258 08D2 16 0 N 0 %
L19
Dehumidification set point RW 2270 08DE 16 0 N 0 %
L23
“Night purging” duration RW 2274 08E2 16 0 N 1 min
L24
“Night purging” set point RW 2275 08E3 16 0 Y 0 °C
L25
“Economy” mode differential RW 2276 08E4 16 0 Y -1 °C
L26
Shutter min. opening CO2 set point RW 2277 08E5 16 0 N 0 %
t01
Inlet air temperature probe (STR) R 4097 1001 16 0 Y -1 °C
t02
Outlet air temperature probe (STM) R 4098 1002 16 0 Y -1 °C
t03
Fluid probe circuit 1 (SL1) R 4099 1003 16 0 Y -1 °C
t04
Outside air temperature probe (STE) R 4100 1004 16 0 Y -1 °C
t05
CO2 probe (CO2) R 4101 1005 16 0 Y 1 ppm
t06
Fluid probe circuit 2 (SL2) R 4102 1006 16 0 Y -1 °C
t07
Inlet air humidity probe (SUR) R 4103 1007 16 0 Y 0 %
t08
Outside air humidity probe (SUE) R 4104 1008 16 0 Y 0 %
- Shutter opening R 14339 3803 16 0 N 0 %
- COOLING mode activated * RW 16525 408D 1 8 N 0 -
- HEATING mode activated * RW 16525 408D 1 9 N 0 -
- Unit status ( 1 = ON ; 0 = OFF ) RW 16525 408D 1 15 N 0 -
- Alarm E00 R 17089 42C1 1 8 N 0 -
- Allarm E02 R 17089 42C1 1 10 N 0 -
- Allarm E05 R 17089 42C1 1 13 N 0 -
- Allarm E06 R 17089 42C1 1 14 N 0 -
- Allarm E07 R 17089 42C1 1 15 N 0 -
- Allarm E22 R 17089 42C1 1 2 N 0 -
-
Allarm E26 R 17089 42C1 1 5 N 0 -
- Allarm E27 R 17089 42C1 1 6 N 0 -
- Allarm E40 R 17091 42C3 1 8 N 0 -
- Allarm E42 R 17091 42C3 1 10 N 0 -
- Allarm E46 R 17091 42C3 1 12 N 0 -
- Allarm E48 R 17091 42C3 1 13 N 0 -
- Allarm E49 R 17091 42C3 1 14 N 0 -
- Allarm E01 - manual reset R 17093 42C5 1 9 N 0 -
- Allarm E02 - manual reset R 17093 42C5 1 10 N 0 -
- Allarm E05 - manual reset R 17093 42C5 1 13 N 0 -
- Allarm E21 - manual reset R 17093 42C5 1 1 N 0 -
- Allarm E22 - manual reset R 17093 42C5 1 2 N 0 -
- Allarm E41 - manual reset R 17095 42C7 1 9 N 0 -
- Allarm E43 - manual reset R 17095 42C7 1 6 N 0 -
- Allarm E63 - manual reset R 17095 42C7 1 2 N 0 -
* If both operating modes are enabled by mistake the unit switches to OFF status.