Installation
Seite/Page 154 - Kaptitel/Chapter 14: Installation 14.7.16
14.4.1 Terminal assignments on the Panda iControl2 controller
14.4.1.1 Terminal assignment of 18-pin connector
Fig. 14.4.1.1-1: Terminal assignment of 18-pin connector
14.4.1.2 Fischer Panda standard bus
Fig. 14.4.1.2-1: Fischer Panda standard bus terminal assignment
14.4.1.3 Fischer Panda CAN bus
Fig. 14.4.1.3-1: Fischer Panda CAN bus terminal assignment
Terminal IN / OUT Function
1 -- Actuator (optional)
2 I Cylinder head temperature
3 IN Exhaust manifold temperature
4 IN Winding temperature
5 IN Reserve temperature
6 IN Oil pressure
7 IN Emergency stop
8 -- GND, ground for all temperature sensors
9--GND
10 -- Actuator (optional)
11 -- +5V servo motor (red wire)
12 OUT PWM servo motor (yellow wire)
13 OUT Booster (optional, depending on generator type)
14 OUT Fuel pump
15 OUT Fuel pump
16 OUT Electric starter
17 OUT Electric starter
18 OUT Electric starter
Terminal Terminal description Function
1 UBUS Bus supply voltage
2 GND Fischer Panda bus ground, ground connection between Panda iControl2 controller and
Panda iControl2 panel
3 REIZ Exciter line,
is switched to ground by the panel if the controller is to switch on
4 DATA+ Fischer Panda bus data line A
5 DATA- Fischer Panda bus data line B
6 UBAT Battery voltage
Terminal Terminal description
Function
1 UBUS Bus supply voltage
2 GND Fischer Panda bus ground, ground connection between iControl2 controller and Panda
iControl2 panel
3REIZ
Exciter line, is switched to ground by the panel if the controller is to switch on
4 CAN-L CAN-Low
5 CAN-H CAN-High
6 UBAT Battery voltage