Maintenance and Troubleshooting HyPower-Geko
116 FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
List of regular maintenance work
The following maintenance tasks must be performed at the indicated time intervals.
Maintenance frequency
Components
Quarterly
Semi-annually
Annually
Before cooling season
Checking filter
x
Checking fan or fan chamber *
x
Variant: checking intake and/or discharge sound attenuator *
x
Checking screw connections of pipes**
x
Checking electrical connections
x
Checking earthing
x
Air venting heat exchanger
x
Checking heat exchanger and main condensate tray for dirt/mold and, if necessary, clean and dis-
infect.
x
Checking fans
x
Checking internal insulation for dirt and mould and, if necessary, cleaning and disinfecting **
x
Checking settings of all valves **
x
Level sensor for drip tray **
x
Checking condensate pump function **
x
* Clean if necessary and remove objects **Depends on the model
Tab. 8-1: Regular maintenance