EasyManua.ls Logo

FläktGroup HYPOWER-GEKO - Unit Venting, Drain Checks, and Network Configuration

FläktGroup HYPOWER-GEKO
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning HyPower-Geko
100 FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
7.3 Vent the unit
To ensure that the exchanger is charged with heating/cooling medium, it must be air
vented.
7.4 Checking the condensate drain
This checkpoint only applies to cooling units without condensate pump!
Condensate forms as a result of unit operation in cooling mode, the same applies to
non-insulated pipes. Check
that the connection of the condensate tray (fig. 7-7, Pos. 1) is performed so that
condensate can drain freely. At the same time a sufficient slope of the condensate
line must be considered.
User instructions!
Protect electrical hardware and furniture from escaping splash water.
Open all shut-off and control valves.
Open the venting screw(s) with a suitable tool
(see fig. 7-6).
Close the air vent screw again only if heating/
cooling medium is still pouring out.
Proceed in the same way with all remaining air
vent screws. Depending on the unit model,
there are additional 1 or 2 air vent screws.
Pos. 1: Air vent screws
Fig. 7-6: Air venting heat exchanger
Pos. 1: Coil drip tray
Pos. 2: Condensate drain
Fig. 7-7: Drainage of the condenser water

Table of Contents

Related product manuals