Installation Multi-DENCO
46 FläktGroup DC-2013-0101-GB • Subject to modifications • R5-08/2020
When the WaterCool Module of W-Version placed away from the main unit, it is nec-
essary to keep the clearance as in the table below:
5.4.2 Access
Multi-DENCO has been designed with service access exclusively through the front
doors of the unit (standard are flat doors). Access to the right hand side panel (as you
face the unit) can increase the speed of service, but is not mandatory.
Multi-DENCO units are compact and efficient design, therefore the larger the clearance
all around the unit, the easier service and repair work can be conducted.
The doors are hinged and removable. Some frame mullions are removable for assist-
ing in removing larger components.
For W-Version, suitable space underneath is required the WaterCool Module and the
main unit to allow them to be connected by the refrigerant pipes.
Size Unit
Width
mm
Unit
Depth
mm
Floor Void
(B)
mm
Service Access
(C)
mm
010 300 600 300 500
018 300 600 300 500
030 510 780 400 500
045 510 780 400 500
065 510 780 500 500
092 700 880 500 700
130 700 880 500 700
Tab. 5-2
Note!
• For P-Version units, it is necessary to keep a minimum gap of 200 mm between the
units for service access.
• Column C is ONLY the minimum service requirements and does not reflect any
health and safety regulations or requirements affecting your installation.