3 General principles
FLUXUS G801 3.4 Undisturbed flow profile
17
UMFLUXUS_G801V1-0EN, 2020-06-26
disturbance: 2 × 90° elbow on different planes
inlet: l 40 D outlet: l 5 D
disturbance: valve
inlet: l 40 D outlet: l 5 D
disturbance: reducer
inlet: l 10 D outlet: l 5 D
disturbance: compressor
inlet: l 20 D
Tab. 3.1: Recommended distance from disturbances
D – nominal pipe diameter at the measuring point
l – recommended distance between disturbance and transducer position
l l
l l
l l
l