7 Connection
7.2 Power supply FLUXUS G801
2020-06-26, UMFLUXUS_G801V1-0EN
70
7 Connection
7.2 Power supply
The installation of the power supply is carried out by the operator. The operator has to provide an overcurrent protector
(fuse or similar device) disconnecting all energizing wires in case of an inadmissible high current consumption. The
impedance of the protective earth has to be low ohmic in order not to allow touch voltage pass the permissible limit. The
equipotential bonding terminal serves as functional earth of the transmitter.
The external protective earth is connected to the equipotential bonding terminal on the transmitter housing.
Connect the power cable to the transmitter (see section 7.2.1, Fig. 7.12 and Tab. Tab. 7.8).
Important!
The degree of protection of the transmitter will only be guaranteed if the power cable fits firmly and tightly in the cable
gland.
Fig. 7.12: Connection of the power supply to the transmitter
1 power supply of transmitter FLUXUS *801**-A10****-AA, *801**-A10****-AP
2 power supply of transmitter FLUXUS *801C24, *801**-A10****-FF
3 equipotential bonding terminal
Tab. 7.8: Terminal assignment
terminal connection AC terminal connection DC
L phase 100…230 V L+ +
N neutral L- -
PE earth PE earth
1
2
FLUXUS *801**-A10****-AA, *801**-A10****-AP FLUXUS *801C24, *801**-A10****-FF
3
3