General: Custom Energy Savings Settings
07 – FORCED 2ND STAGE HEATING*
00-60 (30* default setting) Select a number of minutes 1st stage heating will
run before 2nd stage heating is automatically initiated if the guest set
point is not reached and the 2nd stage heating is not initiated through
differential settings.
This feature allows automatically turning on 2nd stage heating to avoid
excessive compressor use.
Set to 00 to disable the feature.
This also applies as the 3rd and 4th stage differential on top of the 2nd
when there are more than 2 stages.
* If applicable.