Boiler data for planning the flue gas system
Name S3 Turbo
20
1)
30 40 45
Flue gas temperature at nominal
load
°C 150 170 150 170
Flue gas temperature at partial load - 120 110 120
Flue gas mass flow at nominal load kg/s 0.016 0.022 0.028 0.033
Flue gas mass flow at partial load - 0.011 0.013 0.016
Required feed pressure at nominal
load
Pa 8
mbar 0.08
Required feed pressure at partial
load
Pa - 8
mbar - 0.08
Maximum permissible feed pressure Pa 30
mbar 0.3
Flue pipe diameter mm 149
1.Applies for S3 Turbo 18 as well (only available in Italy)