Boiler with manual controller
100%
50%
0%
+
-
Set the manual controller for the air flap as shown in the table below
NOTICE! The information below only applies to split wood and not for round timber,
square timber etc.
Soft wood Hardwood
Long split wood Short split wood Long split
wood
Short split wood
w > 20% w < 20% w > 20% w < 20% w > 20% w < 20% w > 20% w < 20%
PL
1
75-100%
PL
1
75-100%
PL
1
75-100%
PL
1
50%
PL
1
75-100%
PL
1
75-100%
PL
1
75%
PL
1
50%
SL
2
25-50%
SL
2
50-75%
SL
2
50-75%
SL
2
50-75%
SL
2
50%
SL
2
50-75%
SL
2
75-100%
SL
2
75-100%
1.PL = Primary air
2.
SL = Secondary air
If you use wood briquettes for initial start-up (only permitted under certain conditions!),
you can use roughly the same settings as for short split hardwood.
The table shows the setting values for the manual controller of the air flap, which
ensures a smooth start-up. The setting values for the manual controller may need to
be changed during emissions measurements. For this reason, these values should not
be used as standard values for operating the boiler!
The terms used, i.e. “long split wood” (edge length EL > 10 cm) and “short split wood”
(edge length EL < 10 cm), have been defined in these instructions by Froling; there is
no fuel standard or similar guidelines.
Open the insulated door and the fuel loading door
Fill the fuel loading chamber for initial start-up and heat up
NOTICE! See boiler operating instructions
5
Start-up
Initial startup