EasyManuals Logo

Froling S3 Turbo Installation Instructions

Froling S3 Turbo
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
Regulations and standards for permitted fuels
1. BImSchV First Order of the German Federal Government for the
implementation of the Federal Law on Emission Protection
(Ordinance on Small and Medium Combustion Plants) in the
version published on 26 January 2010,
BGBl. JG 2010 Part I No. 4.
EN ISO 17225-3 Solid bio-fuel - Fuel specifications and classes
Part 3: Wood briquettes for non-industrial use
EN ISO 17225-5 Solid bio-fuel - Fuel specifications and classes
Part 5: Firewood for non-industrial use
2.4.2 Installation and approval of the heating system
The boiler should be operated in a closed heating system. The following standards
govern the installation:
EN 12828 - Heating Systems in Buildings
NOTICE! Each heating system must be officially approved.
The appropriate supervisory authority (inspection agency) must always be informed
when installing or modifying a heating system, and authorisation must be obtained
from the building authorities:
Austria: report to the construction authorities of the community or magistrate
Germany: report new installations to an approved chimney sweep / the building
authorities.
2.4.3 General information for installation room (boiler room)
Boiler room characteristics
The floor must be even, clean and dry and have an adequate load-bearing
capacity.
There must not be a potentially explosive atmosphere in the boiler room as the
boiler is not suitable for use in potentially explosive environments.
The boiler room must be frost-free.
The boiler does not provide any light, so the customer must ensure sufficient
lighting in the boiler room in accordance with national workplace design
regulations.
When using the boiler above 2000 metres above sea level you should consult the
manufacturer.
Danger of fire due to flammable materials.
The floor of the boiler room must not be flammable. No flammable materials
should be stored near the boiler. Flammable objects (e.g. clothing) must not be put
on the boiler to dry.
Note on standards
2
Safety
Design Information
8 Froeling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.at

Table of Contents

Other manuals for Froling S3 Turbo

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Froling S3 Turbo and is the answer not in the manual?

Froling S3 Turbo Specifications

General IconGeneral
BrandFroling
ModelS3 Turbo
CategoryBoiler
LanguageEnglish

Related product manuals