Froling S3 Turbo - 4.3 Faults with fault message

Froling S3 Turbo
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Open the door
Insert a sheet of paper at both the top and the bottom of the door stop between
the door and the boiler
Close the door
Try to pull out the sheets of paper
If the paper cannot be removed:
the door is sealed.
If the paper can be removed:
The door is not sealed properly - push the hinge toward the back.
⇨ See "Positioning the doors" [page 31]
On the side with the door handle
Close the door
The door can be closed with a normal amount of effort:
Setting OK
If the door cannot be closed with the usual force or must be forced closed:
Push the locking plate toward the front
⇨ See "Positioning the doors" [page
31]
Checking the seal:
Checking the setting: