Page 83
Three wiring options are available under 16 (EOL):
Norm: Standard GardTec wiring configuration without Mask or Fault detection.
Note: Does not give any Fault or Masking detection and should only be used with Zone pairing.
ELF1: ELF1 wiring is used for detectors that have a relay output (a pair of terminals)
for Fault or Mask..
ELF2: ELF2 wiring is used for detectors that have a transistor output (a single
terminal) for Fault or Mask.
Note: We would recommend that either ELF1 Format or ELF2 Format (dependant on detector output type,
Relay or Transistor) is used. ELF1 or ELF2 wiring modes will allow for Alarm, Tamper, Fault and Masking to be
monitored from a single zone without the need for zone pairing.
Note: The installer should check what output type the detector are, noting that all the detectors should be of the
same type with regards to the Fault / Mask output.
28) Press No until the setting you require is displayed,
then press Yes. The display will show:-
Options available are:-
ZEX = Standard GardTec Zone EXpanders.
(Are all defaulted to EOL with the same options
that are available for the on-board zones).
ID = ID Expander card using ID Biscuits.
Please refer to page 166 for programming ID Expanders - 872 only.
29) With the display showing:-
Press Yes.
30) The display will show:-
Zone Expansion
= ZEX
Radio ZEX
> Off
Zone Expansion
= ZEX
PR5892 Rev11 800 Series Eng Ref 15.qxd 16/11/2006 11:21 Page 83